SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, 8AI, RESOLUTION 9/12/14 BITS, U/I/THERMOCOUPLE/RESISTANCE INTERRUPT, DIAGNOSTICS; 1X20PIN REMOVE/INSERT W. BACKPLANE BUS
|
|
Supply voltage |
Load voltage L+ |
Rated value (DC) |
24 V |
Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
200 mA |
from backplane bus 5 V DC, max. |
50 mA |
Power losses |
Power loss, typ. |
1 W |
Analog inputs |
Number of analog inputs |
8 |
Number of analog inputs for resistance measurement |
4 |
permissible input voltage for voltage input (destruction limit), max. |
20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
Voltage |
Yes |
Current |
Yes |
Thermocouple |
Yes |
Resistance thermometer |
Yes |
Resistance |
Yes |
Input ranges (rated values), voltages |
0 to +10 V |
No |
1 to 5 V |
Yes |
Input resistance (1 to 5 V) |
100 kΩ |
1 to 10 V |
No |
-1 V to +1 V |
Yes |
Input resistance (-1 V to +1 V) |
10 MΩ |
-10 V to +10 V |
Yes |
Input resistance (-10 V to +10 V) |
100 kΩ |
-2.5 V to +2.5 V |
Yes |
Input resistance (-2.5 V to +2.5 V) |
100 kΩ |
-250 mV to +250 mV |
Yes |
Input resistance (-250 mV to +250 mV) |
10 MΩ |
-5 V to +5 V |
Yes |
Input resistance (-5 V to +5 V) |
100 kΩ |
-50 mV to +50 mV |
No |
-500 mV to +500 mV |
Yes |
Input resistance (-500 mV to +500 mV) |
10 MΩ |
-80 mV to +80 mV |
Yes |
Input resistance (-80 mV to +80 mV) |
10 MΩ |
Input ranges (rated values), currents |
0 to 20 mA |
Yes |
Input resistance (0 to 20 mA) |
25 Ω |
-10 to +10 mA |
Yes |
Input resistance (-10 to +10 mA) |
25 Ω |
-20 to +20 mA |
Yes |
Input resistance (-20 to +20 mA) |
25 Ω |
-3.2 to +3.2 mA |
Yes |
Input resistance (-3.2 to +3.2 mA) |
25 Ω |
4 to 20 mA |
Yes |
Input resistance (4 to 20 mA) |
25 Ω |
Input ranges (rated values), thermoelements |
Type B |
No |
Type E |
Yes |
Input resistance (Type E) |
10 MΩ |
Type J |
Yes |
Input resistance (type J) |
10 MΩ |
Type K |
Yes |
Input resistance (Type K) |
10 MΩ |
Type L |
Yes |
Input resistance (Type L) |
10 MΩ |
Type N |
Yes |
Input resistance (Type N) |
10 MΩ |
Type R |
No |
Type S |
No |
Type T |
No |
Type U |
No |
Type TXK/TXK(L) to GOST |
No |
Input ranges (rated values), resistance thermometers |
Cu 10 |
No |
Ni 100 |
Yes; Standard |
Input resistance (Ni 100) |
10 MΩ |
Ni 1000 |
No |
LG-Ni 1000 |
No |
Ni 120 |
No |
Ni 200 |
No |
Ni 500 |
No |
Pt 100 |
Yes; Standard |
Input resistance (Pt 100) |
10 MΩ |
Pt 1000 |
No |
Pt 200 |
No |
Pt 500 |
No |
Input ranges (rated values), resistors |
0 to 150 ohms |
Yes |
Input resistance (0 to 150 ohms) |
10 MΩ |
0 to 300 ohms |
Yes |
Input resistance (0 to 300 ohms) |
10 MΩ |
0 to 600 ohms |
Yes |
Input resistance (0 to 600 ohms) |
10 MΩ |
0 to 6000 ohms |
No |
Thermocouple (TC) |
for thermocouples |
Type E, J, K, L, N |
Temperature compensation |
Parameterizable |
Yes |
internal temperature compensation |
Yes |
external temperature compensation with compensations socket |
Yes |
Resistance thermometer (RTD) |
Characteristic linearization |
for resistance thermometer |
Pt100 (standard, climatic range), Ni100 (standard, climatic range) |
Characteristic linearization |
Parameterizable |
Yes |
Cable length |
Cable length, shielded, max. |
200 m; 50 m at 80 mV and thermocouples |
Analog value creation |
Measurement principle |
integrating |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. |
15 bit; Unipolar: 9/12/12/14 bits; bipolar: 9 bits + sign/12 bits + sign/12 bits + sign/14 bits + sign |
Integration time, parameterizable |
Yes; 2.5/ 16.67/ 20/ 100 ms |
Basic conversion time, ms |
3 / 17 / 22 /102 ms |
Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 / 10 Hz |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer |
Yes |
for current measurement as 4-wire transducer |
Yes |
for resistance measurement with 2-conductor connection |
Yes |
for resistance measurement with 3-conductor connection |
Yes |
for resistance measurement with 4-conductor connection |
Yes |
Errors/accuracies |
Operational limit in overall temperature range |
Voltage, relative to input area |
+/- 1 %; +/-1% (80 mV); +/-0.6% (250 to 1000 mV); +/-0.8% (2.5 to 10 V) |
Current, relative to input area |
+/- 0,7 %; From 3.2 to 20 mA |
Impedance, relative to input area |
+/- 0,7 %; 150, 300, 600 Ohm |
Resistance-type thermometer, relative to input area |
+/- 0,7 %; +/-0.7% (Pt100/ Ni100); +/-0.8% (Pt100 climate) |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input area |
+/- 0,6 %; +/-0.4% (250 to 1000 mV); +/-0.6 % (2.5 to 10 mV); +/-0.7 % (80 mV) |
Current, relative to input area |
+/- 0,5 %; 3.2 to 20 mA |
Impedance, relative to input area |
+/- 0,5 %; 150, 300, 600 Ohm |
Resistance-type thermometer, relative to input area |
+/- 0,6 %; +/-0.5% (Pt100/ Ni100); +/-0.6% (Pt100 climate) |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm |
Yes; Parameterizable, channels 0 and 2 |
Limit value alarm |
Yes; Parameterizable |
Diagnostic messages |
Diagnostic functions |
Yes; Parameterizable |
Diagnostic information readable |
Yes |
Diagnostics |
Yes |
Diagnostics indication LED |
Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
between the channels |
No |
between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 V DC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weight |
Weight, approx. |
250 g |
Recent Comments