Archive for August, 2013

Aug 22 2013

Mitsubishi FX2N-485-BD+ RS485 Board

Introduction to Mitsubishi FX2N-485-BD+

The communication board FX2N-485-BD for RS485 (hereinafter referred to as “485BD”) can be connected to the base unit of the FX2N Series programmable controller to be used for the following applications.
1) Data transfer using no protocol
Data communication with diversified RS232C units including personal computers, bar code readers and printers can be performed via the RS485 (422) converter using the no protocol. In this application, data is sent or received using the data registers specified by the RS instruction. For the setting and program examples, refer to the FX Programming Manual and FX Communication User’s Manual.
2) Data transfer using the dedicated protocol
Data transfer with RS485 (422) units can be performed on the 1:N basis using the dedicated protocol.
For the contents of the dedicated protocol used in this application, refer to the FX Communication User’s Manual.
3) Data transfer using the parallel link
Data transfer with an FX2N programmable controller can be performed on the 1:1 basis for 100 auxiliary relays and 10 data registers. For the setting and program examples, refer to the FX Communication User’s Manual.
4) Data transfer using the N:N network
Data transfer with FX2N programmable controllers can be performed on the N:N basis. For the setting,the number of transferred data and program examples, refer to the FX Communication User’s Manual.

 

1.1 External Dimensions of Mitsubishi FX2N-485-BD+

 

12

 

1.2 System Configuration of Mitsubishi FX2N-485-BD+


1.2.1 No Protocol or Dedicated Protocol of Mistubishi FX2N-485-BD+

13

 

1.2.2 Parallel Link of Mistubishi FX2N-485-BD+

14

 

1.2.3 N:N Network of Mistubishi FX2N-485-BD+

15

 

MUNTING AND WIRING of Mitsubishi FX2N-485-BD+

2.1 Mounting Procedure to Mistubishi FX2N-485-BD+

16

 

2.2  Cable and Terminal Resistor to connect the RS485 FX2N-485-BD+


2.2.1 Cable to connect Mistubishi FX2N-485-BD+
To connect the RS485 (422) unit, use a shielded twisted-pair cable.
The cable specification must be AWG 26 to 16, and the maximum tightening torque must be 0.6 N·m (6 kgf·cm). If a cable other than the AWG 26 to 16 is used, normal communication cannot be assured because the terminal may be imperfectly contacted. It is recommended to insert a cable integrated by the crimping tool into the terminal.


2.2.2 Terminal Resistor of Mistubishi FX2N-485-BD+
Provide the terminal resistor at both ends of the line as described in section 2.3.2 and 2.3.3.
1) In the case of two-pair wiring, connect the terminal resistor (330W, 1/4W) between terminals SDA and SDB as well as between terminals RDA and RDB.

17
Use the resistors offered as accessories of the 485BD.
2) In the case of one-pair wiring, connect the terminal resistor (110W, 1/2W)between terminals RDA and RDB. Use the resistors offered as accessories of the 485BD.

18

 

2.3 Wiring of Mitsubishi FX2N-485-BD+


2.3.1 Selection of Wiring of Mistubishi FX2N-485-BD+
Wiring of RS485 is one-pair wiring or two-pair wiring. The wiring method is decided according to the
usage. Please select the wiring method from the table below.

19

*1 When this product is added to the system, please match the wiring to the wiring method of the system.
*2 When using 485BD with, this wiring method remember to take account of/or ignore the “echo” of the commands sent from the FX2N programmable controller.
*3 Use FX2N programmable controller and 485BD together.
*4 For excluding the combination of 485BD, please see below.

20

 

2.3.2 Two-pair Wiring

21

*1 R is the terminating resistance. Connect the terminating resistance (330W) between terminals SDA and SDB, and terminals RDA and RDB.
*2 The shield of the shielded twisted-pair cable must be connected to ground (100W or less). When using parallel link, ground both side. When using no protocol or dedicated protocol, ground one side.
*3 Connect terminal FG to each terminal of the programmable controller main body grounded with resistance of 100 or less. However, for the computer link unit of the A series programmable controller, see the manual of the computer link unit.
*4 When using RS232/485 or RS232/422 interface, please the use FX-485PC-IF.

 

2.3.3 One-pair Wiring

22

*1 R is the terminating resistance. Connect the terminating resistance (110W) between terminals RDA and RDB.
*2 The shield of the shielded twisted-pair cable must be connected to ground (100W or less). When using parallel link, ground both side. When using no protocol or dedicated protocol, ground one side.
*3 Connect terminal FG to each terminal of the programmable controller main body grounded with resistance of 100 or less. However, for the computer link unit of the A series programmable controller, see the manual of the computer link unit.
*4 When using RS232/485 or RS232/422 interface, please the use FX-485PC-IF.

 

SPECIFICATIONS of Mitsubishi FX2N-485-BD+

3.1 General Specifications of Mitsubishi FX2N-485-BD+
General specifications are the same as those for the FX2N series programmable controller.


3.2 Power Supply Specification of Mitsubishi FX2N-485-BD+
5V DC, 60 mA is supplied from the programmable controller.


3.3 Specification of Mitsubishi FX2N-485-BD+

 Item    Content  
 Transmission standard    Conforming to RS485 and RS422  
 Transmission distance    Max. 50 m  
 LED indicators  

 SD, RD  

 

Item Content
Communication
method
and protocol
N:N network Half-duplex communication
Dedicated protocol
(format 1 or format 4)
Parallel link
No protocol Full-duplex communication
Supported baud rate Dedicated protocol and no protocol: 300 ~ 19,200 (bps)
Parallel link : 19,200 (bps)
N:N network : 38,400 (bps)
Isolation No isolation

 

DIAGNOSTICS of Mitsubishi FX2N-485-BD+

For error code of N:N network and computer link, refer to the FX Communication User’s Manual.


4.1 Common Items
1) Check the connection with the communication unit of the programmable controller and the wiring.
When the connection is unstable, the communication can not be corrected.
2) Check whether the VRRD or VRSC instruction is used in used in the program.
If it is used, delete it, turn off the power of the programmable controller, then turn it on again.
3) Each setting of communication format (D8120), parameter of programmable controller by FX-PCS/WIN-E, N:N network (D8173 to D8180) and parallel link (M8070, M8071) is suitable for the usage or it checks. The communication is not correctly done if setting is not suitable for the usage.
When each setting is changed, please turn off the power supply of the programmable controller, and turn it on again.
4) When you use FX0N-485ADP or FX-485ADP in network, please the power supply for the drive must be supplied correctly or check.


4.2 LED Check Items of Mitsubishi FX2N-485-BD+
4.2.1 N:N Network
1) Check the status of the RD LED and the SD LED provided on each 485BD.
- If both of them are lit and extinguished, nothing is wrong.
- If the RD LED is lit/extinguished but the SD LED is not lit/extinguished (not lit at all), check the setting of the station No.,the baud rate (transmission rate) and the total number of salve stations.
- If the RD LED is not lit/extinguished, check the wiring.
2) Make sure that the communication error (FX2N: M8183 to M8190, FX0N: M504 to M511) in each slave station is not turned on and that the data communication flag (FX2N: M8191, FX0N: M503) is not turned off. When one of the communication error flag is turned on or if the data communication flag is turned off, check the error code of data registers (FX2N: D8211 to D8218, FX0N: D211 to D218).

For the error code, please see the FX Communication User’s Manual. 

 

4.3 Parallel Link
1) Check the status of the RD(RXD) LED and the SD(TXD) LED provided on each communication unit.
- If both of them are lit and extinguished, nothing is wrong.
- If the RD(RXD) LED is lit/extinguished but the SD(TXD) LED is not lit/extinguished (not lit at all),check the setting of the master station and the slave stations.
- If the RD(RXD) LED is not lit/extinguished, check the wiring.
2) Make sure that the master station and the slave stations are set correctly. If the setting is incorrect,correct it.
3) Make sure that the devices for the master station and the slave stations are handled correctly. If they are handled incorrectly, correct the program so that they are handled correctly.


4.4 Computer Link
1) Check the status of the RD(RXD) LED and the SD(TXD) LED provided on each communication unit.
- If both of them are lit and extinguished, nothing is wrong.
- If the RD(RXD) LED is lit/extinguished but the SD(TXD) LED is not lit/extinguished (not lit at all),check the setting of the station No. and the transmission rate (baud rate).
- If the RD(RXD) LED is not lit/extinguished, check the wiring and confirm the connection with the programmable controller.
2) Make sure that the communication procedure is performed correctly. If it is not performed correctly,correct the setting in the computer.
3) Check the NAK error code and programmable controller error code.
For the error code, please see the FX Communication User’s Manual.

 

4.5 RS Instruction
1) Check the status of the RD (RXD) LED and the SD (TXD) LED provided in an optional equipment.
- If the RD (RXD) LED is not lit while data is received or the SD (TXD) LED is not lit while data is sent, check the installation and the wiring.
- When the RD (RXD) LED is lit while data is received or the SD (TXD) LED is lit while data is sent, the installation and the wiring are correct.
2) Make sure the timing of data send/receive. For example, make sure that the counterpart equipment is ready for receive before starting to send data to it.
3) When the terminator is not used, check whether the send data capacity is equivalent to the acceptable data capacity. If the send data capacity may be changed, use the terminator.
4) Make sure that the external equipment is correctly operating.
5) Check whether the type of send data and the type of receive data are equivalent. If they are different,make them equivalent.
6) When two or more RS instructions are used in the program, make sure that only one RS instruction is actuated in one operation cycle. Never turn off the RS instruction while data is received or sent.
7) In the FX2N Series (V2.00 or later), an RS instruction is not executed if the counterpart equipment receives “NAK”.
Arrange the system so that the RS instruction is executed even if the counterpart equipment receives “NAK”.

 

Our company (Kollewin Technology CO., Limited) have new products.

Named FX2N-485-BD+ .

They are 100% compatible with Mitsubishi original FX2N-485-BD.

 

 

Part#:FX2N-485-BD+

 

The unit price is USD62.89/pc buy buttom

 

USER'S MUNUAL PDF of communication board FX2N-485-BD

FX2N-485-BD-USER'S MANUAL

 

FX2N-485-BD

 

FX2N-485-BD+

 

Specification of communication board FX2N-485-BD+:

Product Name Communication Board
Fit for Mitsubishi FX2N PLC
Model NO. FX2N-485-BD
Interface Conforming to RS485 and RS422
Connector Type Mini Din 8 Pin
Voltage DC 5V
Current 60mA
Max.Transmission Distance 50M
LED Indicators SD, RD
Communication Method Half-duplex
Insulation No Insulated
Material Plastic, Metal

 

Description of communication board FX2N-485-BD+:

  • FX2N are suitable for use with FX2N PLC's. FX2N-232-BD are used for RS-485 applications, such as communication with a PC, printer or bar code reader. and provide a second programming port which enables an operator panel (or HMI) and a programming panel to be connected to the PLC at the same time.
  • This is a Replacement of Mitsubishi FX2N-485-BD Programmable Controller.
  • This is OEM product, not Mitsubishi original part.

 

More communication boards we have

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

FX2N-4DA

 

More pictures of PLC communication board

FX1N-USB-BD-1 FX3U-USB-BD FX3U-CNV-BD FX3U-485-BD FX3U-422-BD FX3U-232-BD FX2N-422-BD FX2N-USB-BD-1 FX1N-422-BD FX1N-485-BD FX2N-232-BD

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com
Aug 21 2013

6ED1 057-1AA00-0BA0 Siemens LOGO!PC-CABLE

  Introduction to LOGO!PC-CABLE 6ED1057-1AA00-0BA0

LOGO! PC CABLE, F. THE TRANSMISSION OF PROGRAMS FROM PC TO LOGO! AND VICE VERSA
 

Technic data of  LOGO!PC-CABLE 6ED1057-1AA00-0BA0:

  4
LOGO! PC CABLE, F. THE TRANSMISSION OF PROGRAMS FROM PC TO LOGO! AND VICE VERSA
 
Cables
belongs to product LOGO!
Cable length 3 m
Weight
Weight, approx. 168 g

 

Product related properties of  LOGO!PC-CABLE 6ED1057-1AA00-0BA0
Title German LOGO! RS232 PC Kabel
Title English LOGO! RS232 PC cable
Type of object (content) Product photo
Search term(s)  
Search items/synonyms
German
Logikmodul LOGO!
Search items/synonyms
English
Logic module LOGO!
Product family LOGO!
Order number (e.g. 1AB1234-1AB12) 6ED1057-1AA00-0BA0

 

6ED1057-1AA00-0BA0

 

 

Our company (Kollewin Technology CO., Limited) have a new product,

 

named LOGO!PC-CABLE,

it is 100% compatible with Siemens original part 6ED1 057-1AA00-0BA0.


Part#: LOGO!PC-CABLE

Unit price: USD43.00/pc  buy buttom

Description: RS232 isolated cable
Manufacturer: Kollewin

Approx. Weight: 0.3 Kg
Warranty: 1 year
Origin: China

 

RS232 optoelectronic isolated programming cable for  Siemens LOGO!,3 meters,

can replace Siemens 6ED1 057-1AA00-0BA0

logo-PC cable_1

More pictures of our compatible cables of Siemens parts :

CP5512_1 CP5611-A2_1 CP5512E_1 PC-TTY_1 0CB20-1 V6.0_1 USB-MPI V5.0_1 USB-MPI+V4.0_1 USB-MPI+V2.0_1      

 

Other compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

More pictures for your reference:

USB-CN226 _1 USB-CIF02_1 TSXPCX3030_1 IC690USB901_1 IC690ACC901_1 USB-1761-CBL-PM02_1 1747-PIC_1 1747-UIC_1 USB-SC09_1 USB-QC30R2 1 ES-ETH-SC09 1 USB-SC09-FX_1 FX-USB-AW 1         

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com

 

Aug 20 2013

PC-TTY Siemens 6ES5 734-1BD20

Introduction to 6ES5 734-1BD20

SIMATIC S5 734-1 CABLE FROM PLC, 15-PIN TO PC, 25-PIN 3.2M
 
Data sheet of 6ES5 734-1BD20
 
  
SIMATIC S5 734-1 CABLE FROM PLC, 15-PIN TO PC, 25-PIN 3.2M
 
Cables
belongs to product SIMATIC S5
Cable length 3.2 m
Weight
Weight, approx. 278 g
 

 

Our company (Kollewin Technology CO., Limited) have a new product,

named PC/TTY.

It is 100% compatible with Siemens original part.

 

Part#: PC/TTY

EX-Work Price: $45.00/pc       buy buttom

Approx. Weight: 0.3Kg
Manufacturer: Kollewin
Warranty: 1 year
Origin: China

 

PC-TTY_1

 

Specifications of PC/TTY 

This is a good replacement OEM cable for Siemens S5 PLC.
Replace Siemens part # 6ES5 734-1BD20.
Use for communication between Siemens S5 series PLC and PC .

 

 

More compatible PLC Programming cables of Siemens

CP5611

CP5611-A2

CP5512

CP5512EXP-NEW

PC Adapter CN-NEW

ES-ETH-PPI-NEW

ETH Adapter CN-NEW

USB/PPIM+

PC/PPI

PC/PPI+

USB/MPI+ V4.0

USB/MPI+ V2.0

PC/MPI+ including RS232 cable

PC/MPI

LOGO!USB-CABLE

LOGO!PC-CABLE

MPI extension cable

PC/TTY

 

More pictures of our compatible cables of Siemens parts :

CP5512_1 CP5611-A2_1 CP5512E_1 PC-TTY_1 0CB20-1 V6.0_1 USB-MPI V5.0_1 USB-MPI+V4.0_1 USB-MPI+V2.0_1      

 

Other compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

More pictures for your reference:

USB-CN226 _1 USB-CIF02_1 TSXPCX3030_1 IC690USB901_1 IC690ACC901_1 USB-1761-CBL-PM02_1 1747-PIC_1 1747-UIC_1 USB-SC09_1 USB-QC30R2 1 ES-ETH-SC09 1 USB-SC09-FX_1 FX-USB-AW 1         

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com
 
Aug 19 2013

CP5512 Express Card for Siemens 6GK1551-2AA00

Introduction to 6GK1551-2AA00

COMMUNICATION PROCESSOR CP 5512 PC CARD (CARDBUS, 32 BITS) FOR CONNECTION OF A PG OR NOTEBOOK TO PROFIBUS OR MPI

 

Data sheet of 6GK1551-2AA00

Product-type designation CP 5512
     2
COMMUNICATION PROCESSOR CP 5512 PC CARD (CARDBUS, 32 BITS) FOR CONNECTION OF A PG OR NOTEBOOK TO PROFIBUS OR MPI
Transmission rate  
Transmission rate  
  • at interface 1 / in accordance with PROFIBUS
 
  • minimum
9.6 kbit/s
  • maximum
12 Mbit/s
Interfaces  
Number of electrical connections / at interface 1 / in accordance with PROFIBUS 1
Design of electrical connection / at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS 485)
Supply voltage, current consumption, power loss  
Type of voltage DC
Supply voltage  
  • 1 / from backplane bus
3.3 V
Relative symmetrical tolerance  
  • at 3.3 V / with DC
5 %
Consumed current  
  • 1 / from backplane bus / with DC / maximum
0.52 A
Resistive loss 1.8 W
Permitted ambient conditions  
Ambient temperature  
  • during operating
5…45 °C
  • during storage
-20…+60 °C
  • during transport
-20…+60 °C
Relative humidity  
  • at 25 °C / without condensation / during operating / maximum
95 %
Protection class IP IP00
Design, dimensions and weight  
Width 86 mm
Height 5 mm
Depth 54 mm
Net weight 130 g
Product properties, functions, components / general  
Number of plug-in cards in the same design / can be plugged in / per PC station 1
Number of modules / note -
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum 50
Software / for DP master function / required Yes, SOFTNET-PB DP
Service / as DP master  
  • DPV0
Yes
  • DPV1
No
  • DPV2
No
Number of DP slaves / on DP master / usable 64
Amount of data  
  • of the address area of the inputs / as DP master / overall
7808 byte
  • of the address area of the outputs / as DP master / overall
7808 byte
  • of the address area of the inputs / per DP slave
244 byte
  • of the address area of the outputs / per DP slave
244 byte
  • of the address area of the diagnostic data / per DP slave
244 byte
Service / as DP slave  
  • DPV0
Yes
  • DPV1
No
Amount of data  
  • of the address area of the inputs / as DP slave / overall
122 byte
  • of the address area of the outputs / as DP slave / overall
122 byte
Number of possible connections / for S7/PG communication / maximum 8
Number of configurable connections / per PC station 207
Configuration software / required NCM PC is included in scope of delivery of the required software product
Product function / Port diagnostics Yes
Standards, specifications, approvals  
Standard  
  • for EMC
2004/108/EC
  • for safety / of CSA and UL
CAN/CSA C22.2 & UL 60950-1
  • for emitted interference
EN 61000-6-3, EN 61000-6-4
  • for interference immunity
EN 61000-6-1, EN 61000-6-2
Verification of suitability  
  • CE mark
Yes
  • C-Tick
Yes

 

 

More details of CP5512E, please find in below PDF file:

Communication card CP5512 Siemens S7-200-300-400 6GK1551-2AA00

 

Our company (Kollewin Technology CO., Limited) have a new product,

named CP5512E.

It is 100% compatible with Siemens original part.

Part#: CP5512E

EX-Work Price: $475.00/pc       buy buttom

 

CP5512E_1

 

User's manual PDF of CP5512Express card 6GK1551-2AA00:

 

CP5512 Express 6GK1551-2AA00

 

It's tested before shippment.Not made by Siemens,OEM product as the replacement.

The quality is guaranteed, we have 1 year warranty for our compatible products.

 

Introduction to our CP5512 Express card:

Nowadays the laptops have eliminated the PCMCIA slot,but adopt the ExpressCard slot.So we especially develop the CP5512 EXPRESS for ExpressCard laptop.

ExpressCard CP5512,it’s suitable for Laptop Expresscard slot,is used to achieve PROFIBUS/MPI/PPI/FWLcommunication between PC and SIMATIC Net. Communication speed is 9.6Kbps–12Mbps.It can be also used for desktop computer after the conversion card.

Not inlcude the MPI extension cable,for MPI cable,please click this link to get: MPI Cable

The function of our CP5512 EXPRESS is the totally same as Siemens original CP5512 except they use on different laptop interfaces.It’s the isolated PROFIBUS/MPI/PPI/FWL communication card specially for laptop, use iCoupler Magnetic Coupling isolators to replace the optocoupler,with small  dimension, wide temperature range,and have anti-lightning and surging protective circuit and resumption of Overcurrent protection circuit on the RS485 interface, all use industrial IC in order to apply to wider temperature range, is used to achieve PROFIBUS/MPI/PPI/FWL communication connection between laptop and SIMATIC.

CP5512 EXPRESS also can be used on PCI-E slot of desktop computer after the PCI-E to ExpressCard converter, the function is same as Siemens CP5611,CP5621.

CP5512 EXPRESS support hot plug and plug and play. Perfect isolation circuit and interface protective circuit make you at ease to use it.

 

Communication service:                                                               

PROFIBUS-DP master station class 1 and 2
PROFIBUS-DP slave and SOFTNET-DP slave
MPI/PPI/FWL communication
S7 communication with SOFTNET-S7
S5-compatible communication (SEND/RECEIVE based on the FDL interface) with SOFTNET-D or SOFTNET-S7

 

CP5512 EXPRESS is suitable for the following version or above version softwares:
STEP7  V5.2
SOFTNET-S7  V6.1
SOFTNET-DP, SOFTNET-DP slave from V6.1
STEP 7-Micro/WIN from V3.2 SP4
ProTool®, ProTool/Pro® V6.0 SP2
NCM PC from V5.2
SIMATIC PDM V5.2 SP1

 

Technical Specification:                                                                           

Transmission rate: 9.6Kbps~12Mbps,the corresponding largest communication distance accord with PROFIBUS standard.
Interface:connect PROFIBUS/MPI/PPI,isolated 9 pin Sub-D connector.

Isolated voltage:1000VDC

Interface protection:have anti-lightning and surging protection(Ipp=100A 10/700us,4KV) on the RS485 interface.ITU-TK20/21,VDE 0433 standard. ±15KV ESD protection. Overcurrent protection with  restoration function:RS485 port can withstand up to 60V voltage caused by continuous over-current.

Standard working voltage:3.3 VDC
power:1.0W
working temperature:-20~+75℃
size:adapter:length* width * height(mm):123×68×30,cable length:  25CM
weight:150g

 

Support hardware of CP5512 EXPRESS:

It’s different from PC Adapter and PC Adapter USB, CP5512 EXPRESS supports much more hardwares,such as Siemens S7-200/300/400PLC, PPI/MPI/PROFIBUS interface of touch panel, EM277,ET200 and other hardwares with PROFIBUS/MPI/PPI/FWL interface.

It need PROFIBUS cable or MPI cable(Siemens part nr 6ES7 901-0BF00-0AA0) when CP5512 EXPRESS communicates with fieldbus devices.

 

Signal definition of CP5512 EXPRESS profibus Interface(DB9F):

 

Pin No.

Signal name

Description

Input / Output

1

NC

Unused

-

2

NC

Unused

-

3

B(RXD+/TXD+) RS485 Signal+ Input/Output

4

RTS_AS

Handshake signal

Input

5

Ground(0V) Signal Ground -

6

+5V 5V power 50mA.max. output

7

NC

Unused

-

8

A(RXD-/TXD-) RS485 Signal- Input/Output

9

RTS_PG Request Output

Shell

PE Shield -
 

 

More compatible PLC Programming cables of Siemens

 

CP5611

CP5611-A2

CP5512

CP5512EXP-NEW

PC Adapter CN-NEW

ES-ETH-PPI-NEW

ETH Adapter CN-NEW

USB/PPIM+

PC/PPI

PC/PPI+

USB/MPI+ V4.0

USB/MPI+ V2.0

PC/MPI+ including RS232 cable

PC/MPI

LOGO!USB-CABLE

LOGO!PC-CABLE

MPI extension cable

PC/TTY

 

More pictures of our compatible cables of Siemens parts :

CP5512_1 CP5611-A2_1 CP5512E_1 PC-TTY_1 0CB20-1 V6.0_1 USB-MPI V5.0_1 USB-MPI+V4.0_1 USB-MPI+V2.0_1      

 

Other compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

 

 

More pictures for your reference:

USB-CN226 _1 USB-CIF02_1 TSXPCX3030_1 IC690USB901_1 IC690ACC901_1 USB-1761-CBL-PM02_1 1747-PIC_1 1747-UIC_1 USB-SC09_1 USB-QC30R2 1 ES-ETH-SC09 1 USB-SC09-FX_1 FX-USB-AW 1         

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com
 
Aug 18 2013

CP5512 card for Siemens 6GK1551-2AA00

Introduction to 6GK1551-2AA00

COMMUNICATION PROCESSOR CP 5512 PC CARD (CARDBUS, 32 BITS) FOR CONNECTION OF A PG OR NOTEBOOK TO PROFIBUS OR MPI

 

Data sheet of 6GK1551-2AA00

 
Product-type designation CP 5512
   2
COMMUNICATION PROCESSOR CP 5512 PC CARD (CARDBUS, 32 BITS) FOR CONNECTION OF A PG OR NOTEBOOK TO PROFIBUS OR MPI
Transmission rate  
Transmission rate  
  • at interface 1 / in accordance with PROFIBUS
 
  • minimum
9.6 kbit/s
  • maximum
12 Mbit/s
Interfaces  
Number of electrical connections / at interface 1 / in accordance with PROFIBUS 1
Design of electrical connection / at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS 485)
Supply voltage, current consumption, power loss  
Type of voltage DC
Supply voltage  
  • 1 / from backplane bus
3.3 V
Relative symmetrical tolerance  
  • at 3.3 V / with DC
5 %
Consumed current  
  • 1 / from backplane bus / with DC / maximum
0.52 A
Resistive loss 1.8 W
Permitted ambient conditions  
Ambient temperature  
  • during operating
5…45 °C
  • during storage
-20…+60 °C
  • during transport
-20…+60 °C
Relative humidity  
  • at 25 °C / without condensation / during operating / maximum
95 %
Protection class IP IP00
Design, dimensions and weight  
Width 86 mm
Height 5 mm
Depth 54 mm
Net weight 130 g
Product properties, functions, components / general  
Number of plug-in cards in the same design / can be plugged in / per PC station 1
Number of modules / note -
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum 50
Software / for DP master function / required Yes, SOFTNET-PB DP
Service / as DP master  
  • DPV0
Yes
  • DPV1
No
  • DPV2
No
Number of DP slaves / on DP master / usable 64
Amount of data  
  • of the address area of the inputs / as DP master / overall
7808 byte
  • of the address area of the outputs / as DP master / overall
7808 byte
  • of the address area of the inputs / per DP slave
244 byte
  • of the address area of the outputs / per DP slave
244 byte
  • of the address area of the diagnostic data / per DP slave
244 byte
Service / as DP slave  
  • DPV0
Yes
  • DPV1
No
Amount of data  
  • of the address area of the inputs / as DP slave / overall
122 byte
  • of the address area of the outputs / as DP slave / overall
122 byte
Number of possible connections / for S7/PG communication / maximum 8
Number of configurable connections / per PC station 207
Configuration software / required NCM PC is included in scope of delivery of the required software product
Product function / Port diagnostics Yes
Standards, specifications, approvals  
Standard  
  • for EMC
2004/108/EC
  • for safety / of CSA and UL
CAN/CSA C22.2 & UL 60950-1
  • for emitted interference
EN 61000-6-3, EN 61000-6-4
  • for interference immunity
EN 61000-6-1, EN 61000-6-2
Verification of suitability  
  • CE mark
Yes
  • C-Tick
Yes

 

More details of CP5512, please find in below data sheet:

Communication card CP5512 Siemens S7-200-300-400 6GK1551-2AA00

 

Our company (Kollewin Technology CO., Limited) have a new product,

named CP5512.

It is 100% compatible with Siemens original part.

Part#: CP5512

EX-Work Price: $365.00/pc       buy buttom

CP5512_1

 

User's manual PDF of CP5512 6GK1551-2AA00:

CP5512 introduction 6GK1551-2AA00

 

It's tested before shippment.Not made by Siemens,OEM product as the replacement.

The quality is guaranteed, we have 1 year warranty for our compatible products.

 

Description of our compatible CP5512:

SIMATIC NET communication card for laptop,correspond to Siemens 6GK1551-2AA00,optoelectronic isolated,anti-lightning and surging,suitable for laptop PCMCIA 32bit CardBus slot,is used to achieve PROFIBUS/MPI/PPI/FWL communication connection between PC and SIMATIC,communication speed is 9.6Kbps~12Mbps.After switched over by the transition card,it can be used for desk computer and secondary generation ExpressCard slot laptop.CP5512 +(PCI->PCMCIA) transition card,then can be used for desk computer; CP5512 + (PCMCIA(II)->PCMCIA)transition card,then can be used for secondary generation ExpressCard slot laptop.

If you want to directly buy the CP5512 expresscard,please click this link to get: CP5512-Express
Not made by Siemens,OEM product

Not including MPI extension cable for card communication,if you also need this,please also order it:MPI Cable

 

Introduction of our CP5512:
CP5512 is the isolated PROFIBUS/MPI/PPI/FWL communication card specially for laptop, use iCoupler isolators eliminate optocoupler limitations instead of Photoelectric isolation,with small  dimension, wide temperature range,and have anti-lightning and surging protective circuit and Overcurrent protection with  restoration function on the RS485 interface, all use industrial IC in order to apply to wider temperature range, is used to achieve PROFIBUS/MPI/PPI/FWL communication connection between laptop and SIMATIC.
CP5512 insert laptop PCMCIA slot from outside. Its function and Features is the same as Siemens original CP5512(Siemens part nr 6GK1551-2AA00 ),and have the following new characters.

1. Card and RS485 adapter integrative design, small dimension, use conveniently and have anti-lightning and surging protective circuit on the RS485 interface.

2.Support hot plug, you can plug or unplug the card when the laptop is running. And card and adapter is integrated, so it’s not like original CP5512 which exist the hidden trouble that destroy the card when plug or unplug the card from the adapter with current.

3.Support common Express to PCMCIA transition card. You can use it on the Express slot laptop.

4.Support common PCI to PCMCIA transition card. You can use it on the desk computer and the function is the same as Siemens original CP5611 and CP5611 A2.
 

Communication service:
PROFIBUS-DP master station class 1 and 2
PROFIBUS-DP slave with SOFTNET-DP slave
MPI/PPI/FWL communication
S7 communication with SOFTNET-S7
S5-compatible communication (SEND/RECEIVE based on the FDL interface) with SOFTNET-DP or SOFTNET-S7

 

CP5512 can be used with: 
STEP7  V5.2
SOFTNET-S7  V6.1
SOFTNET-DP, SOFTNET-DP slave from V6.1
STEP 7-Micro/WIN from V3.2 SP4
ProTool®, ProTool/Pro® V6.0 SP2
NCM PC from V5.2
SIMATIC PDM V5.2 SP1

 

Technical Specification of CP5512:
Transmission rate: 9.6Kbps~12Mbps,the corresponding largest communication distance accord with PROFIBUS standard.
Interface:connect PROFIBUS/MPI/PPI,isolated 9 pin Sub-D connector.
Isolated voltage:1000VDC
Interface protection:have anti-lightning and surging protection(Ipp=100A 10/700us,4KV) on the RS485 interface.ITU-TK20/21,VDE 0433 standard. ±15KV ESD protection. Overcurrent protection with  restoration function:RS485 port can withstand up to 60V voltage caused by continuous over-current.
Standard working voltage:3.3 VDC
power:1.0W
working temperature:-20~+75℃
size:length* width * height(mm):130×54×5(DB9F plug height:22mm)
weight:70g

CP5512
 

Support hardware of CP5512:
It’s different from PC Adapter and PC Adapter USB, CP5512 supports much more hardwares,such as Siemens S7-200/300/400PLC, PPI/MPI/PROFIBUS interface of touch panel, EM277,ET20 and other hardwares with PROFIBUS/MPI/PPI/FWL interface.
It need PROFIBUS cable or MPI cable(Siemens part nr 6ES7 901-0BF00-0AA0) when CP5512 communicates with fieldbus devices.


 

 Signal definition of CP5512 Interface:

 

 

Pin No.  Signal name  Description  Input / Output

 

 

 

 

 

 

 

 

1

NC Unused -
2 NC Unused -
3 B(RXD+/TXD+) RS485 Signal+ Input/Output
4 RTS_AS Handshake signal Input
5 Ground(0V) Signal Ground -
6 +5V 5V Power 50mA.max. Output
7 NC Unused -
8 A(RXD-/TXD-) RS485 Signal- Input/Output
9 RTS_PG Request Output
Shell PE Shield -
 
 

More compatible PLC Programming cables of Siemens

CP5611

CP5611-A2

CP5512

CP5512EXP-NEW

PC Adapter CN-NEW

ES-ETH-PPI-NEW

ETH Adapter CN-NEW

USB/PPIM+

PC/PPI

PC/PPI+

USB/MPI+ V4.0

USB/MPI+ V2.0

PC/MPI+ including RS232 cable

PC/MPI

LOGO!USB-CABLE

LOGO!PC-CABLE

MPI extension cable

PC/TTY

 

More pictures of our compatible cables of Siemens parts :

CP5512_1 CP5611-A2_1 CP5512E_1 PC-TTY_1 0CB20-1 V6.0_1 USB-MPI V5.0_1 USB-MPI+V4.0_1 USB-MPI+V2.0_1      

 

Other compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

 

More pictures for your reference:

USB-CN226 _1 USB-CIF02_1 TSXPCX3030_1 IC690USB901_1 IC690ACC901_1 USB-1761-CBL-PM02_1 1747-PIC_1 1747-UIC_1 USB-SC09_1 USB-QC30R2 1 ES-ETH-SC09 1 USB-SC09-FX_1 FX-USB-AW 1         

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com

 

Aug 17 2013

CP5611-A2 card for Siemens 6GK1561-1AA01

Introduction to 6GK1561-1AA01 (CP5611-A2)

COMMUNICATION PROCESSOR CP 5611 A2 PCI-CARD (32 BIT; 3.3/5V;33/ 66 MHZ) FOR CONNECTION TO PG OR PC WITH PCI-BUS TO PROFIBUS OR MPI (NO WIN9X-SUPPORT!) CURRENTLY ONLY 32BIT SUPPORT IN CONNECTION WITH SIMATIC NET V8.2 SW!

 
Data sheet of 6GK1561-1AA01.
 
Product-type designation CP 5611 A2
  1
COMMUNICATION PROCESSOR CP 5611 A2 PCI-CARD (32 BIT; 3.3/5V;33/ 66 MHZ) FOR CONNECTION TO PG OR PC WITH PCI-BUS TO PROFIBUS OR MPI (NO WIN9X-SUPPORT!) CURRENTLY ONLY 32BIT SUPPORT IN CONNECTION WITH SIMATIC NET V8.2 SW!
Transmission rate  
Transmission rate  
  • at interface 1 / in accordance with PROFIBUS
 
  • minimum
9.6 kbit/s
  • maximum
12 Mbit/s
Interfaces  
Number of electrical connections / at interface 1 / in accordance with PROFIBUS 1
Design of electrical connection / at interface 1 / in accordance with PROFIBUS 9-pin Sub-D socket (RS 485)
Supply voltage, current consumption, power loss  
Type of voltage DC
Supply voltage  
  • 1 / from backplane bus
5 V
Relative symmetrical tolerance  
  • at 5 V / with DC
5 %
Consumed current  
  • 1 / from backplane bus / with DC / maximum
0.5 A
Resistive loss 2.5 W
Permitted ambient conditions  
Ambient temperature  
  • during operating
5…55 °C
  • during storage
-20…+60 °C
  • during transport
-20…+60 °C
Relative humidity  
  • at 25 °C / without condensation / during operating / maximum
95 %
Protection class IP IP00
Design, dimensions and weight  
Width 18 mm
Height 102 mm
Depth 130 mm
Net weight 100 g
Product properties, functions, components / general  
Number of plug-in cards in the same design / can be plugged in / per PC station 1
Number of modules / note -
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum 50
Software / for DP master function / required Yes, SOFTNET-PB DP
Service / as DP master  
  • DPV0
Yes
  • DPV1
Yes
  • DPV2
No
Number of DP slaves / on DP master / usable 64
Amount of data  
  • of the address area of the inputs / as DP master / overall
14640 byte
  • of the address area of the outputs / as DP master / overall
14640 byte
  • of the address area of the inputs / per DP slave
244 byte
  • of the address area of the outputs / per DP slave
244 byte
  • of the address area of the diagnostic data / per DP slave
244 byte
Service / as DP slave  
  • DPV0
Yes
  • DPV1
No
Amount of data  
  • of the address area of the inputs / as DP slave / overall
122 byte
  • of the address area of the outputs / as DP slave / overall
122 byte
Number of possible connections / for S7/PG communication / maximum 8
Number of configurable connections / per PC station 207
Configuration software / required NCM PC is included in scope of delivery of the required software product
Product function / Port diagnostics Yes
Standards, specifications, approvals  
Standard  
  • for EMC
89/336/EEC
  • for safety / of CSA and UL
CAN/CSA C22.2 & UL 60950-1, UL 1950
  • for emitted interference
EN 61000-6-3
  • for interference immunity
EN 61000-6-2
Verification of suitability  
  • CE mark
Yes
  • C-Tick
Yes
Accessories  
Accessories optional: MPI cable
 
 
More details of CP5611-A2, please find in below data sheet:
CP5611-A2 communication card 6GK1561-1AA01

 

Our company (Kollewin Technology CO., Limited) have a new product,

named CP5611-A2.

It is 100% compatible with Siemens original part.

Part#: CP5611-A2

EX-Work Price: $259.00/pc       buy buttom

 CP5611-A2_1

 

User's manual PDF of CP5611-A2 communication card 6GK1561-1AA01:

CP5611-A2 communication card 6GK1561-1AA01

 

It's tested before shippment.Not made by Siemens,OEM product as the replacement.

The quality is guaranteed, we have 1 year warranty for our compatible products.

 
 
 
Description of our compatible communication card CP5512-A2:

CP5611-A2 communications cards which is Anti-lightning and anti-surge, corresponding to the Siemens 6 GK1 561-1AA01, photoelectric isolation, and applied to desktop computer's PCI slots, to achieve the PROFIBUS DP / MPI / PPI communications between PC or PG and the SIMATIC network, communication rate is 9.6 Kbps ~ 12Mbps.

 

Not made by Siemens,OEM product

Not including MPI extension cable for card communication,if you also need this,please also order it:

MPI Cable

 

Overview of communication card CP5611-A2:
CP5611-A2 communication card is optoelectronic isolated design for industrial applications.There is anti-lightning & anti-surging protection circuit and over-current protection on the RS485 port.The adoption of industrial chip applies to a wide temperature range. CP5611-A2 card is used to achieve the PROFIBUS DP / MPI / PPI communication between PC or PG and the SIMATIC network.

 

Communication services:
PROFIBUS-DP master grade 1 and 2
PROFIBUS-DP slave and SOFTNET-DP slave
MPI/PPI communication
PG/OP communication
S7 communication with SOFTNET-S7

S5-compatible communication (SEND/RECEIVE based on the FDL interface) with SOFTNET-DP or SOFTNET-S7

 

CP5611-A2 applies to the following software:
STEP7 V.52 and above
SOFTNET-S7
SOFTNET-DP
SOFTNET-DP slave
COM PROFIVUS V3.3 and above
STEP 7-Micro/WIN V3.1 and above
ProTool, ProToo/Pro
NCMPC

 

Technical specifications of communication card CP5512-A2:

Transmission rate:9.6Kbps~12Mbps, corresponding maximum communication distance conforms to PROFIBUS standard
Interface: PROFIBUS/MPI/PPI, isolated 9-pin Sub-D socket
Isolation Voltage: 1000VDC
RS485 port with anti-lightning and anti-surging protector, repeatability surge capacity: Ipp = 100A (10/700us, 4KV)
Standard: ITU-TK20/21, VDE 0433. ± 15KV ESD (ESD) protection
Over-current protection: RS485 interface can withstand up to 60V voltage caused by the sustained over-current
PG/PC connection: PCI2.1 standard slot
Standard voltage: +5 VDC
Power: 2.0W
Operating temperature: 0 ~ + 70 'C
Size (width x high) (mm): 102 x 130
Weight: 100g

 

We also have other compatible PLC Programming cables of Siemens

CP5611

CP5611-A2

CP5512

CP5512EXP-NEW

PC Adapter CN-NEW

ES-ETH-PPI-NEW

ETH Adapter CN-NEW

USB/PPIM+

PC/PPI

PC/PPI+

USB/MPI+ V4.0

USB/MPI+ V2.0

PC/MPI+ including RS232 cable

PC/MPI

LOGO!USB-CABLE

LOGO!PC-CABLE

MPI extension cable

PC/TTY

 

Here, more pictures of our compatible cables of Siemens parts

0CB20-1 V6.0_1 PC-TTY_1 CP5512_1 CP5512E_1 logo-usb cable_1 logo-PC cable_1 USB-MPI+V2.0_1 USB-MPI+V4.0_1 USB-MPI V5.0_1 ETH Adapter CN PC Adapter CN

 
 

Of course, we also supply some other brands compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

 

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

Pictures for your reference:

FX1N-USB-BD-1 FX3U-232-BD FX2N-USB-BD-1 USB-CN226 _1 USB-CIF02_1 TSXPCX3030_1 IC690USB901_1 IC690ACC901_1 USB-1761-CBL-PM02_1 1747-PIC_1 1747-UIC_1 USB-SC09_1 USB-QC30R2 1 ES-ETH-SC09 1 USB-SC09-FX_1 FX-USB-AW 1

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com
Aug 16 2013

CP5611 card for Siemens 6GK1561-1AA00

Introduction to 6GK1561-1AA00 (CP5611)

COMMUNICATION PROCESSOR CP 5611 PCI CARD (32 BIT) FOR CONNECTION OF A PG OR PC WITH PCI BUS TO PROFIBUS OR MPI

 

Data sheet of Siemens original 6GK1561-1AA00:

Product-type designation CP 5611
   1
COMMUNICATION PROCESSOR CP 5611 PCI CARD (32 BIT) FOR CONNECTION OF A PG OR PC WITH PCI BUS TO PROFIBUS OR MPI

 

More details of CP5611, please find in below data sheet:

6GK1561-1AA00 CP5611 manual

 

Our company (Kollewin Technology CO., Limited) have a new product,

named CP5611.

It is 100% compatible with Siemens original part.

Part#: CP5611

EX-Work Price: $190.00/pc       buy buttom

CP5611-A2_1

 

User's manual PDF of CP5611 communication card 6GK1561-1AA00:

CP5611 Card introduction card 6GK1561-1AA00

 

It's tested before shippment.Not made by Siemens,OEM product as the replacement.

The quality is guaranteed, we have 1 year warranty for our compatible products.

 

Decription of our compatible communication card CP5611:

CP5611 communications cards which is Anti-lightning and anti-surge, corresponding to the Siemens 6 GK1 561-1AA00, photoelectric isolation, and applied to desktop computer's PCI slots, to achieve the PROFIBUS DP / MPI / PPI communications between PC or PG and the SIMATIC network, communication rate is 9.6 Kbps ~ 12Mbps.

 

Not made by Siemens,OEM product

Not including MPI extension cable for card communication,if you also need this,please also order it:

MPI cable

 

Overview of communication card CP5611:
CP5611 communication card is optoelectronic isolated design for industrial applications.There is anti-lightning & anti-surging protection circuit and over-current protection on the RS485 port.The adoption of industrial chip applies to a wide temperature range. CP5611 card is used to achieve the PROFIBUS DP / MPI / PPI communication between PC or PG and the SIMATIC network.

 

Communication services:
PROFIBUS-DP master grade 1 and 2
PROFIBUS-DP slave and SOFTNET-DP slave
MPI/PPI communication
PG/OP communication
S7 communication with SOFTNET-S7

S5-compatible communication (SEND/RECEIVE based on the FDL interface) with SOFTNET-DP or SOFTNET-S7

 

CP5611 applies to the following software:
STEP7 V.52 and above
SOFTNET-S7
SOFTNET-DP
SOFTNET-DP slave
COM PROFIVUS V3.3 and above
STEP 7-Micro/WIN V3.1 and above
ProTool, ProToo/Pro
NCMPC

 

Technical specifications of communication card CP5611:

Transmission rate:9.6Kbps~12Mbps, corresponding maximum communication distance conforms to PROFIBUS standard
Interface: PROFIBUS/MPI/PPI, isolated 9-pin Sub-D socket
Isolation Voltage: 1000VDC
RS485 port with anti-lightning and anti-surging protector, repeatability surge capacity: Ipp = 100A (10/700us, 4KV)
Standard: ITU-TK20/21, VDE 0433. ± 15KV ESD (ESD) protection
Over-current protection: RS485 interface can withstand up to 60V voltage caused by the sustained over-current
PG/PC connection: PCI2.1 standard slot
Standard voltage: +5 VDC
Power: 2.0W
Operating temperature: 0 ~ + 70 'C
Size (width x high) (mm): 102 x 130
Weight: 100g

 

We also have other compatible PLC Programming cables of Siemens

CP5611

CP5611-A2

CP5512

CP5512EXP-NEW

PC Adapter CN-NEW

ES-ETH-PPI-NEW

ETH Adapter CN-NEW

USB/PPIM+

PC/PPI

PC/PPI+

USB/MPI+ V4.0

USB/MPI+ V2.0

PC/MPI+ including RS232 cable

PC/MPI

LOGO!USB-CABLE

LOGO!PC-CABLE

MPI extension cable

PC/TTY

 

Here, more pictures of our compatible cables of Siemens parts

ETH Adapter CN PC Adapter CN logo-PC cable_1 PC-TTY_1 0CB20-1 V6.0_1 CP5512_1 CP5512E_1 logo-usb cable_1 USB-MPI+V2.0_1 USB-MPI+V4.0_1 USB-MPI V5.0_1

 

Of course, we also supply some other brands compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

Pictures for your reference:

USB-CN226 _1 USB-CIF02_1 TSXPCX3030_1 IC690USB901_1 IC690ACC901_1 USB-1761-CBL-PM02_1 1747-PIC_1 1747-UIC_1 USB-SC09_1 USB-QC30R2 1 ES-ETH-SC09 1 USB-SC09-FX_1 FX-USB-AW 1

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com

 

Aug 15 2013

PC Adapter CN RS232 to PROFIBUS/MPI adapter

Introduction to PC Adapter CN

This adapter is compatible with Siemens PC Adapter and HMI adapter,fully support  RS232 port of PC and HMI to PROFIBUS/MPI communication, use the Siemens special protocol processing chip,it can be used for Siemens S7-300/400 series PLC and other equipments with PROFIBUS/MPI interface. RS232-RS485-power supply are all optical isolated, especially suitable for the strong interference and communication interface easily damaged industrial scene.

 PC Adapter CN

 

It is 100% compatible with Siemens original part.

 

Part#: PC Adapter CN

EX-Work Price: $286.00/pc       buy buttom

Approx. Weight: 0.3Kg
Manufacturer: Kollewin
Warranty: 1 year
Origin: China

 

User's manual PDF of PC Adapter CN:

PC Adapter CN USER MANUAL

 

It's tested before shippment.Not made by Siemens,OEM product as the replacement.

The quality is guaranteed, we have 1 year warranty for our compatible products


PC Adapter CN is a high-tech adapter compatible with Siemens PC Adapter and HMI Adapter,fully support RS232 serial port of PC and HMI to PROFIBUS/MPI communication, adopt the Siemens protocol processor chip,no functional defects. PC Adapter CN is the opto-isolated adapter for industrial design.It has the surge protection and anti-lightning protection circuit on the RS232 interface and RS485 interface, support hot plug, is suitable for Siemens S7-300/400 series PLC and other equipments with PROFIBUS/MPI interface. In particular, it applies to the strong interfere industrial situations and the safeguard in the circuit guarantees the safely running of the system.
PC Adapter CN can communicate between S7-300/400PLC and RS232 interface of third party HMI,can replace the Siemens HMI Adapter.

The low version PC/MPI+ didn’t adopt the Siemens protocol processor chip,but adopt the MCU and use the software to achieve the profibus protocol,the protocol is not perfect and has the defect,only support MPI communication,not support profibus communication,can only connect few HMI and have the defect. When there are many nodes or third-party device in the network,it can’t identify every node. At the same time, it may have the risk that PC/MPI+ can’t be used after the PLC internal program is upgraded in the future.
Main Technical Specifications:

The network type and baud rate which PC Adapter CN supports:

Transmission rate

MPI

PPI

PROFIBUS

DP

Standard

Universal

9.6Kbps

-

-

19.2Kbps

-

45.45Kbps

-

-

93.75Kbps

-

-

187.5Kbps

-

500Kbps

-

-

1.5Mbps

-

 

RS232 serial port baud rate which PC Adapter CN supports:

Transmission rate

RS232-PC

RS232-HMI

 
 
9.6Kbps

(1)

 
19.2Kbps

 
38.4Kbps

 
57.6Kbps

(1)

 
115.2Kbps

(1)

 

 

Note:You only can choose 19.2Kbps and 38.4Kbps baud rate in the STEP7 software,if you need to use other baud rates,it needs the tool software.

 

The following is the comparison between PC Adapter CN and other similar products:

      Model

Function

PC Adapter CN

 

PC/MPI+

 

PC Adapter

SIEMENS

HMI Adapter

SIEMENS

SSW7

Helmholz

PPI-Bus
9.6Kbps

-

-

-

-

-

19.2Kbps

-

-

-

-

-

187.5Kbps

-

-

-

-

-

MPI-Bus
19.2Kbps

187.5Kbps

1.5Mbps

-

-

PROFIBUS
9.6 Kbps

-

-

19.2 Kbps

-

-

45.45 Kbps

-

-

93.75 Kbps

-

-

187.5 Kbps

-

-

500 Kbps

-

-

1.5 Mbps

-

-

3 Mbps

-

-

-

-

-

6 Mbps

-

-

-

-

-

12 Mbps

-

-

-

-

-

PROFIBUS-Profil
DP

-

-

Standard

-

-

Universal(DP/FMS)

-

-

RS232-PC
9.6Kbps

-

19.2Kbps

38.4Kbps

57.6Kbps

-

115.2Kbps

-

RS232-HMI
9.6Kbps

-

-

-

19.2Kbps

-

-

38.4Kbps

-

-

57.6Kbps

-

-

-

115.2Kbps

-

-

-

● RS232 interface can connect PC or HMI etc third party devices,baud rate 9.6Kbps~115.2Kbps automatically adjust.
● Support PROFIBUS and MPI communication, auto bus protocol test,largest baud rate 1.5Mbps.
● Power supply from PLC port,24VDC, Power Consumption 2W,with over current and surge protection.
● Power-RS485-RS232 all isolated
● Opto-isolated voltage 1000VDC.
● RS232 interface has the anti-surging protection
● RS485 interface has the anti-lightning and surging protector, Repeatability surge capacity: Ipp=100A(10/700us,4KV),meet the standard ITU-TK20/21、VDE 0433. ±15KV ESD protection.
● Need additional 24VDC power for the long distance communication, the largest cable length meets the profibus standard.
● With the power indicator, data sending indicator, data receiving indicator
Can install the adapter on the S7-300/400PLC rail or 35MM standard rail.
● Shape Size: 123mm×68mm×30mm(Length*Width*Height),with the mounting bracket
● Working Temperature: -20~+75℃

 

We also have other compatible PLC Programming cables of Siemens

CP5611

CP5611-A2

CP5512

CP5512EXP-NEW

PC Adapter CN-NEW

ES-ETH-PPI-NEW

ETH Adapter CN-NEW

USB/PPIM+

PC/PPI

PC/PPI+

USB/MPI+ V4.0

USB/MPI+ V2.0

PC/MPI+ including RS232 cable

PC/MPI

LOGO!USB-CABLE

LOGO!PC-CABLE

MPI extension cable

PC/TTY

 

Here, more pictures of our compatible cables of Siemens parts

ETH Adapter CN 0CB20-1 V6.0_1 PC-TTY_1 CP5512_1 CP5611-A2_1 CP5512E_1 logo-usb cable_1 logo-PC cable_1 USB-MPI+V2.0_1 USB-MPI+V4.0_1 USB-MPI V5.0_1

Of course, we also supply some other brands compatible PLC Programming cables, such as Mitsubishi/OMRON/Panasonic/GE/Fuji/Schneider/Allen-Bradley/Delta/Proface…

ES-ETH-SC09-NEW

FX-USB-AW

USB-SC09

USB-SC09-FX

SC-09+

SC-10

USB-QC30R2

FX2N-485-BD+

FX2N-485-BD

FX2N-422-BD

FX2N-232-BD

FX1N-485-BD

FX1N-422-BD

FX3U-485-BD

FX3U-422-BD

FX3U-232-BD

FX3U-USB-BD

1747-PIC

1747-UIC

1747-CP3

USB-1747-CP3 

1761-CBL-PM02

USB-1761-CBL-PM02

 

Pictures for your reference:

FX-USB-AW 1 USB-SC09-FX_1 ES-ETH-SC09 1 USB-QC30R2 1 USB-SC09_1 1747-UIC_1 1747-PIC_1 USB-1761-CBL-PM02_1 IC690ACC901_1 IC690USB901_1 TSXPCX3030_1 USB-CIF02_1 USB-CN226 _1

 

Please feel free to contact me for any question!

Contact person: Miss Nancy

Skype: kollewin
E-mail: nancy@kollewin.com
Tel: +86-0755-26898905-8006
Website: www.kollewin.com
Aug 3 2013

Siemens 6ES7222-1HF22-0XA0 digital module

  

Introduction to Siemens 6ES7222-1HF22-0XA0 

6ES7222-1HF22-0XA0                   EM222, 8DO RELAIS, 2A
SIMATIC S7-200, DIGITAL OUTPUT EM 222, FOR S7-22X CPU ONLY, 8DO, (RELAY OUTPUTS) 2A
 

Data sheet of Siemens 6ES7 222-1HF22-0XA0

 

SIMATIC S7-200, DIGITAL OUTPUT EM 222, FOR S7-22X CPU ONLY, 8DO, (RELAY OUTPUTS) 2A
 
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 5 V
permissible range, upper limit (DC) 30 V
Load voltage L1
Rated value (AC) 24 V; 24 to 230 V AC
permissible range, lower limit (AC) 5 V
permissible range, upper limit (AC) 250 V
permissible frequency range, lower limit 47 Hz
permissible frequency range, upper limit 63 Hz
Input current
from backplane bus 5 V DC, max. 40 mA
Digital outputs
from load voltage L+, max. 72 mA; 9 mA per switched output
Power losses
Power loss, typ. 2 W
Digital outputs
Number/binary outputs 8; Relay
Functionality/short-circuit strength No; to be provided externally (see manual package "Setting up an S7-200")
Limitation of inductive shutdown voltage to to be provided externally (see manual package "Setting up an S7-200")
Output current
for signal "1" permissible range for 0 to 40 °C, max. 2 A
for signal "1" permissible range for 0 to 55 °C, max. 2 A
for signal "0" residual current, max. 0 mA
Aggregate current of outputs (per group)
all mounting positions
up to 40 °C, max. 8 A
maximum current per conductor/group 8 A
horizontal installation
up to 55 °C, max. 8 A
Relay outputs
Number of operating cycles, max. 10000000; mechanically 10 million, at rated load voltage 100,000
Switching capacity of contacts
with inductive load, max. 2 A
on lamp load, max. 200 W
Switching frequency/contacts/at ohmic load/maximum 2 A
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Galvanic isolation
Galvanic isolation digital outputs
Galvanic isolation digital outputs Yes; Relay
between the channels, in groups of 4
Connection method
Plug-in I/O terminals Yes
Dimensions
Width 45 mm
Height 80 mm
Depth 62 mm
Weight
Weight, approx. 170 g
 

Our company have the compatible product, named 222-1HF22-0XA0.

Part#: 222-1HF22-0XA0

Unit price:USD57.00/pc  buy buttom
Description: S7-200 module
Manufacturer: Kollewin
Approx. Weight: 0.3 Kg
Warranty: 1 year
Origin: China

 

It's tested before shippment.Not made by Siemens,OEM product as the replacement.

The quality is guaranteed, we have 1 year warranty for our compatible products.

 

Discriptions of our compatible OEM product 222-1HF22-0XA0:

Model

EM222  8 outputs Relay

Product  Description 8DO,24V DC/250V ACRelay; high immunity
The bus current consumption 60mA
Power loss 3W
Number of digital outputs 8
Signal output type· Relay
Isolation Relay
Rated voltage 24V DC or 250V AC
Permissible voltage range 5~30V DC,20~250V AC
Rated current 2.0A
Lamp load 30W DC/200W AC
Cable Length (Shielded) 500m
Cable Length (unshielded) 150m
Switching frequency 1Hz
Lifetime contact mechanical 10,000,000
Lifetime contact mechanical(rated load voltage) 100,000
Dimensions(W x H x D)(mm) 46×80×62
Order Number 222-1HF22-0XA0

 

Please contact us for any problem.